Vue de la page 0
All input connections in one single area
High coolant temperature shutdown
Low oil pressure shutdown
Low coolant level automatic shutdown
Low fuel pressure
Overspeed automatic shutdown
Adjustable cranking timer
Adjustable exercise timer
Oil drain extension
Cool flow radiator
Closed coolant recovery system
• UV/Ozone resistant hoses
Watertight state of the art electrical connectors
Mainline circuit breaker
Oil drain extension to frame rail
Radiator drain extension
Battery charge alternator
2 Amp static battery charger
Battery, battery rack and battery cables
Fan and belt guards
• Isochronous governor
Flex fuel line pigtail
STANDARD EQUIPMENT
Innovative design and fully prototype tested
UL 2200 Listed
Solid state frequency compensated voltage regulator
Dynamic and static battery charger
Sound attenuated acoustically designed enclosure
Whisper-Test™ for low noise level exercise
Acoustically designed engine cooling system
High flow low noise factory engineered exhaust system
State of the art digital control system with H-100
microprocessor control panel
Built-in kW, kVAR and power factor meters
Watertight electrical connectors
Rodent proof construction
High efficiency, low distortion Generac designed alternator
Vibration isolated from mounting base
Matching Generac transfer switches engineered and
tested to work as a system
All components easily accessible for maintenance
Electrostatically applied powder paint
FEATURES
130 kW 60 Hz
Liquid Cooled Gas Engine Generator Sets
Standby Power Rating
GENERAC 6.8L ENGINE
Naturally Aspirated
Gaseous Fueled
Whisper-Test
Low Speed Exercise
65 dB(A) at 23 feet
UL 2200 Listed
COMMERCIAL SERIES
Transfer Switch is sold separately
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - 130 kW 60 Hz

• All input connections in one single area• High coolant temperature shutdown• Low oil pressure shutdown• Low coolant level automatic shutdown• L

Page 2 - COMMERCIAL 130 kW

APPLICATION& ENGINEERING DATARating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage.

Page 3 - OPERATING DATA

COMMERCIAL 130 kW KW RATING 130ENGINE SIZE 6.8 Liter V-10GENERATOR OUTPUT VOLTAGE/KW - 60Hz KW AMP CB Size 120/240V, single phase, 1.0 pf 130

Page 4 - INSTALLATION LAYOUT

COMMERCIAL 130 kWINTERCONNECTIONSINSTALLATION LAYOUT NOTE: Door access from both sidesUNIT WEIGHT: Steel 2873 lbs., Aluminum 2699 lbs. © 2007 Generac